Position : Home > FAQ

Fault code

fault type

Possible causes of failure

Fault countermeasures

oCI

博乐彩票开奖Over current when inverters speed up

 

The load is too heavy and the acceleration time is too short。

Extend acceleration time

V/F curve is not suitable

Adjust V/F curve settings.

Restart the rotating motor

Set to check speed restart function

Torque set value is too large

Adjust manual torque to automatic torque

Inverter power is too small

Use inverter with high power

oCd

Over current when inverters slow down

 

 

 

 

 

 

Deceleration time is too short

Extend deceleration time

Potential load or large inertia load

Increase the braking power of the external energy consumption brake

博乐彩票开奖Inverter power is small

Use inverter with high power

oCo

Over current when the inverter is running at constant speed

Sudden change in load

Check or reduce the load mutation

Acceleration and deceleration time setting is too short

Appropriately extend acceleration and deceleration time

Abnormal load

Check load

Low power grid voltage

Check input power

Inverter power is small

Use inverter with high power

oUI

Over voltage when inverters speed up

Abnormal

Input voltage

Check input power

Acceleration time setting is too short

Appropriately extend acceleration time

Restart the rotating motor

Set to check speed restart function

 

 

 

 

Fault code

fault type

Possible causes of failure

博乐彩票开奖Fault countermeasures

oUd

 

 

博乐彩票开奖Over voltage when inverters slow down

 

Deceleration time setting is too short

博乐彩票开奖Appropriately extend Deceleration time

Potential load or large inertia load

Increase the braking power of the external energy consumption brake

oUo

博乐彩票开奖Over voltage when the inverter is running at constant speed

Abnormal

Input voltage

Check input power

Acceleration and deceleration time setting is too short

Appropriately extend acceleration and deceleration time

Abnormal

Input voltage

Install input reactor

Large load inertia

Use energy consumption brake

oUC

Control power over voltage

Abnormal

Input voltage

Check the input power or seek the service

oH

 

Inverter over heat

博乐彩票开奖Air duct obstruction

博乐彩票开奖Clean up the duct or improve the ventilation conditions.

 High environmental temperature 

Improve ventilation conditions, reduce the carrier frequency

Fan damage

Replace fan

Abnormal inverter module

Seek the service

oLI

Inverter overload

Acceleration time setting is too short

Appropriately extend acceleration time

DC brake capacity is too large

Reduce the DC braking current and prolong the braking time.

V/F curve is not suitable

Adjust the V/F curve and the torque boost

Restart the rotating motor

Set to check speed restart function

Low power grid voltage

Check power grid voltage

Load is too large

博乐彩票开奖Use inverter with high power

oLd

 

 

 

Motor

Overload

 

 

 

 

V/F curve is not suitable

Adjust the V/F curve and the torque boost

Power grid voltage is to small

博乐彩票开奖Check power grid voltage

General Motors long term operation with low speed and large load

 Choose variable frequency motor for long term low speed operation

 

The motor overload protection coefficient setting is not correct

 

Correctly set the motor overload protection coefficient

博乐彩票开奖Motor blocking or load mutations are too large

Check load

LU

Low voltage when running

博乐彩票开奖Power grid voltage is too low

博乐彩票开奖Check the power grid voltage

fault code

fault type

博乐彩票开奖Possible causes of failure

Fault countermeasures

IP

Inverter module protection

Over current

See over current countermeasures

Output three phase short circuit or grounding short circuit

To rewire

博乐彩票开奖Air duct blockage or fan damage

Clean the air duct or replace the fan

high environmental temperature 

reduce the environmental temperature 

博乐彩票开奖Control panel connection or plug loose

Check and reconnect

Abnormal current waveform caused by output phase lack

Check wiring

Auxiliary power supply damage, and drive voltage is low

Seek the manufacturer or agent service

Abnormal control panel

Seek the manufacturer or agent service

oE

External device failure

博乐彩票开奖External fault emergency stop and terminal closure

博乐彩票开奖disconnect external fault terminal after handle external fault

CCE

Current detection and circuit fault

Control panel connection or plug loose

Check and reconnect

Auxiliary power supply damage

Seek the manufacturer or agent service

Hall device damage

Seek the manufacturer or agent service

Abnormal amplifier circuit

Seek the manufacturer or agent service

CE

 

RS232/485

Communication failure

The baud rate is set incorrectly

Set the appropriate baud rate

Serial port communication error

Press    button to reset, and seek the service

Fault alarm parameter setting is improper

Modify d3.09 ~ d3.12 settings

The upper machine does not work

Check whether the upper machine is working or not, and whether the connection is correct or not

CFI

System interference

Serious interference

Push button reset or add the power supply filter on the external side of power input

Master control board DSP read and write error

Push button reset and seek service

EPE

Error in reading and writing

Error in reading and writing control parameters

Push button reset and seek service